8.11 Replacing the BACNET-GW
The CGW-MB and the BACNET-GW-3 have different addressing schemes. Refer to the
Compatible Equipment
Ensure that the replacing CGW-MB has correct object addresses and the old object
mappings of BACNET-GW-3 are removed.
Refer to the
BACnet PIC Statement
1. Ensure that the BACnet feature in the CGW-MB is licensed.
2. Go to CGW-MB Web Configuration Tool.
3. Click the BACnet Settings tab.
4. Ensure that the below BACnet settings are same in the CGW-MB:
• Static IP address
• BACnet Port Number
• Foreign device configurations
• Node mapping
• Network Number
5. Delete the replaced BACnet CLSS Gateway mainboard related objects on the BACnet
client.
6. Connect the CGW-MB.
7. Rediscover the BACnet objects.
Or
Restart the BACnet client.
8. Modify the client graphics according to the rediscovered objects.
8.12 Using Both the CGW-MB and the Legacy BACnet CLSS Gateway
mainboard
The CGW-MB and the BACNET-GW-3 have different addressing schemes. Ensure that
they are assigned with their own addressing scheme.
Refer to the
BACnet PIC Statement
1. Ensure that the BACnet feature in the CGW-MB is licensed.
2. Go to CGW-MB Web Configuration Tool.
3. Click the BACnet Settings tab.
4. Configure the BACnet settings in the new CGW-MB.
Refer to the
5. Connect the CGW-MB and rediscover the BACnet objects.
6. Modify the client graphics according to the new instance numbers (object addresses).
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
Click to set Priorities of Events
Click to set Priorities of Events
Click to set Priorities of Events
Click to set Priorities of Events
Click to set Priorities of Events
Click to set the priorities to default
section for the supported objects details.
To Configure the BACnet Settings
Action
section for the CGW-MB object addressing details.
section for the CGW-MB object addressing details.
section for the configuring procedure.