BACnet PIC Statement
Status Flags
Out of Service
Standard Object Types Supported - Multi-State Input /Multi-State Output / Multi-State Value
Present Value
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
BACnet Status
Boolean
0,0,0,0
Normal
1,0,0,0
InAlarm
0,1,0,0
Fault
0,0,0,1
OutOfService
1,0,0,1
InAlarm,
OutOfService
0,1,0,1
Fault,
OutOfService
Boolean
0
FALSE
1
TRUE
BACnet
Enumeration
1
None
2
None
3
None
4
None
Flags
Normal
Fire Alarm, Security Alarm
(Life/Property), Critical Process Alarm
(Life/Property), Medical Emergency,
PreAlarm, IB Smash Glass, Panic
Alarm
Security Trouble, Fire Trouble, Non-
Fire Trouble
Fire Device or Zone Disabled, Non-
Fire Device Disabled
If device is in Alarm state (Fire Alarm,
Security Alarm (Life/Property), Critical
Process Alarm (Life/Property),
Medical Emergency, PreAlarm, IB
Smash Glass, Panic Alarm) and also
device goes to disable state(Fire
Device or Zone Disabled, Non-Fire
Device Disabled)
If device is in trouble state (Security
Trouble, Fire Trouble, Non-Fire
Trouble )and also device goes to
disable state(Fire Device or Zone
Disabled, Non-Fire Device Disabled)
All statuses other than disable
Fire Device or Zone Disabled, Non-
Fire Device Disabled
Normal
All statuses other than those
included in 3 and 4 below.
Security Trouble, Fire Trouble, Non-
Fire Trouble
Fire Device or Zone Disabled, Non-
Fire Device Disabled
The BACnet Feature
Fire Panel State
Fire Panel State
Fire Panel State
124