Hide thumbs Also See for XV300:
Table of Contents

Advertisement

7.3.2 Disposal

Ambient climatic conditions
Air pressure (in operation)
Temperature
Mounting position
Storage / Transport -20 – + 60 °C (-4 – +140 °F)
Relative humidity
Condensation non-condensing
Before commissioning
If storing/transporting the device in cold weather conditions or in
such a way that it will be exposed to extreme differences in tem-
perature, make sure that no condensation forms on or inside the
device.
If there is condensation in or on the HMI panel, do not switch on the
device until it is completely dry.
Use the original packaging to ship the device.
The XV300 is sturdily built, but the components inside it are sensitive to excessively
strong vibrations and/or mechanical shock.
Accordingly, make sure to protect the XV300 from mechanical loads that exceed the
scope of the unit's intended use.
The XV300 should only be transported in its original packaging after being packed prop-
erly.
EXPLOSION HAZARD
LITHIUM BATTERY
The lithium battery inside the XV300 may explode if handled incorrectly.
XV300  04/19 MN048017EN  www.eaton.eu
7.3 Storage, transport and disposal
795 - 1080 hPa
max. 2000 m a. NHN (standard elevation zero)
 
Operation
± 0 – +50 °C (+32 – +122 °F)
XV-303-10-..., XV-303-70-...
α ≦ ± 45°, T ≦ 50 °C (122 °F)
α
α
 
XV-303-15-.E.-..., XV-303-15-.02-..
α ≦ ± 10°, T ≦ 50 °C (122 °F)
 
XV-303-15-.00-...
α ≦ ± 10°, T ≦ 50 °C (122 °F)
α ≦ ± 45°, T ≦ 45 °C (113 °F)
Inclination from vertical: α ≦ ± 45° at operating temperature ≦ 45°C
possible (if using natural convection)
Relative humidity 10 - 95 %
7. Maintenance
77

Advertisement

Table of Contents
loading