CAUTION
POINTY, SHARP OBJECTS AND CORROSIVE LIQUIDS
When cleaning the XV300:
 
Do not use any pointy or sharp objects (e.g., knives).
l
 
Do not use aggressive or abrasive cleaning products or solvents.
l
Make sure that no liquids get into the XV300 unit (short-circuit hazard)
and that the XV300 unit is not damaged in any way.
CAUTION
INSTALLATION CUT-OUT
The mounting cutout must be located in a position that will not defeat the
purpose of stabilizing webs or other reinforcing elements in the control
panel. If necessary, reinforcing elements must be installed/added.
An IP65, Nema 4x and Nema 12 degrees of protection will only be
ensured if there is sufficient stiffness, the device is properly mounted
using the original fixing material, and the gasket has a proper seat
 
Minimum sheet thickness of control panel panel where the device
l
will be flush mounted:
XV-303-70-.., XV-303-10-..
2 mm (0.08") ≦ d ≦ 5 mm (0.2")
XV-303-15-..
1.5 mm (0.06") ≦ d ≦ 4 mm (0.16")
CAUTION
When using commercially available peripheral devices (e.g., with the
USB port), it is important to keep in mind that their EMC interference
immunity parameters may render them unsuitable for use in industrial
environments.
The USB ports (USB host and USB device) on the XV300 multi touch dis-
play unit are meant for maintenance work only.
WARNING
The device should only be run with safety extra-low voltage (functional
extra-low voltage with protective separation).
The power transformer must meet all applicable standards.
CAUTION
FORCES ON THE ETHERNET INTERFACE
Communications may be affected, and the connection's mechanical
components may be damaged, if the Ethernet interface is subjected to
strong vibrations or the RJ45 plug-in connection is subjected to pulling.
XV300  04/19 MN048017EN  www.eaton.eu
2. Safety regulations
2.3 Device-specific Hazards
33