5.5.2.2 RS-485 topology
5.5 Serial interfaces for communication with PLCs or devices
 
A bus segment can interconnect up to 32 slaves.
l
 
Several bus segments can be connected using repeaters (bi-directional amplifiers).
l
The use of repeaters enables the maximum cable length to be
increased.
For more details, please consult the documentation provided by man-
ufacturer.
A bus segment must be provided with cable termination (120 Ohm) at both ends.
These terminals must be connected in the plug directly between pin 3 and 7.
The bus segment must be terminated at both ends.
No more than two terminations must be provided for each bus seg-
ment.
Operation without correct cable termination can cause transfer
errors.
 
1
6
2
7
A
120
3
B
8
4
9
5
GND

Figure 33: Bus segment with four nodes

XV300  04/19 MN048017EN  www.eaton.eu