Can-Bus-Topology; Figure 34: Can Bus Segment With Four Nodes - Eaton XV300 Manual

Hide thumbs Also See for XV300:
Table of Contents

Advertisement

5.6.0.2 CAN-Bus-topology

The maximal baud rate depends on the cable length
Possible baud rates
When preparing connections, ensure that the cable shield has a low
impedance connection with the connector housing.
 
A bus segment can interconnect up to 32 slaves.
l
 
Several bus segments can be connected using repeaters (bi-directional amplifiers).
l
The use of repeaters enables the maximum cable length to be
increased.
Repeaters can also be used for galvanic isolation. For more details,
please consult the documentation for repeaters provided by man-
ufacturer.
 
Make sure to follow the recommendations provided by CiA (CAN in
Automation)
at http://www.can-cia.org.
A bus segment must be provided with cable termination (120 Ohm) at both ends.
These terminals must be connected in the plug directly between pin 2 and 7.
The bus segment must be terminated at both ends.
No more than two terminations must be provided for each bus seg-
ment.
Operation without correct cable termination can cause transfer
errors.

Figure 34: CAN bus segment with four nodes

XV300  04/19 MN048017EN  www.eaton.eu
5.6 CAN1 interface for protocols CANopen and J1939
With a max. cable length
25 m
of
50 m
100 m
M 250
500 m
500 m
1000 m
2500 m
5000 m
5. External connections
1000 kBit/s (= default settings)
800 kBit/s (= default settings)
500 kBit/s (= default settings)
250 kBit/s (= default settings)
125 kbit/s
100 kBit/s (can be set through soft-
ware)
50 kBit/s (= default settings)
20 kBit/s (= default settings)
10 kBit/s (= default settings)
65

Advertisement

Table of Contents
loading

Table of Contents