3. Installation
3.4 Preparing the device for operation
50
The XV300 multi touch display has an internal fuse and protection against polarity
reversal.
The power supply for the XV300 multi touch display is not galvanically isolated.
The XV300 multi touch display requires a rated operating voltage of 24 VDC from an AC-
to-DC converter with safe isolation (SELV/PELV).
Power supply
rated operating voltage
Permissible voltage range
Voltage dips
Power consumption
XV-303-70-.., XV-313-70-.. max. 14.4 W
XV-303-10-.., XV-313-10-.. max. 18 W
XV-303-15-.. max. 21,6 W
fuse
Potential isolation
Electrical current
XV300  04/19 MN048017EN  www.eaton.eu
+ 24 VDC SELV (safety extra low voltage)/PELV (protective extra low voltage)
Effective: 19.2-30.0 V DC (rated operating voltage -20%/+25%)
Absolute with ripple: 18.0-31.2 V DC
Battery powered: 18.0-31.2 V DC (rated operating voltage -25%/+30%); 35 V  
DC for a duration of < 100 ms
Ability to accommodate brief voltage dips
≦ 10 ms from rated operating voltage (24 V DC), ≦ 5 ms from undervoltage (19.2
V DC)
 
Current consumption at 24 V DC: 11.9 W for basic device + 2.5 W for USB mod-
ule
Current consumption at 24 V DC: 15.5 W for basic device + 2.5 W for USB mod-
ule
Current consumption at 24 V DC: 19,1 W for basic device + 2,5 W for USB mod-
ule
Yes (fuse not accessible)
No
7.0" display
10.1" display
Ie
0.6 A
≦0.75 A
I
1.0 A²s
1.0 A²s
TH
15.6" display
≦ 0.9 A
1.0 A²s