Functional Earthing Xv300; Figure 25: Screwing The Functional Earth Con; Table 11: Specification Functional Earthing - Eaton XV300 Manual

Hide thumbs Also See for XV300:
Table of Contents

Advertisement

3.4.1 Functional earthing XV300

CAUTION
SAFELY DIVERTING ELECTRICAL INTERFERENCE CURRENTS
HMI panel XV300The must be connected to a central earth point with a
conductor that is as short and has as low a resistance as possible.
 
Ground connection characteristics:
l
Wire cross-sectional area ≧ 1.5 mm², length ≦ 350 mm
The XV300 needs to be connected to the conductive structure in, e.g.,
the control panel using the central earth point (earthing screw). This
method of earthing is mandatory required for proper function.
Assemble and terminate the functional earth conductor in advance.
Unscrew the earthing screw on the enclosure.
Put the earthing connection cable's eyelet in position.
Use a torque of 1.3 Nm (11.5 lb-in) to tighten the earthing screw on the enclosure.

Table 11: specification Functional earthing

Functional earthing specifications
Cross section
Earthing bolt
Ring-cable ferrule for M4
Cable length
tightening torque
Functional earthing
Figure 25: Screwing the functional earth conductor onto the enclosure
 
XV300  04/19 MN048017EN  www.eaton.eu
3.4 Preparing the device for operation
≧ 1.5 mm 2
≦ AWG16
PZ2, M4 x 8
Internal diameter = 4.3 mm
External diameter ≦ 8 mm
≦ 350 mm
1.3 Nm (11.5 lb-in)
3. Installation
 
51