Function Code 02 - Read Input Status; Function Code 03 - Read Holding Registers; Function Code 04 - Read Input Registers; Table 15 Address Ranges Of Function Codes - ABB M101 Manual

Interface manual modbus
Table of Contents

Advertisement

FU N CT IO N CO D E 0 2 – R E A D INPU T STAT US
Function codes and their relevant address range are shown in the table below.
Function Codes
FC02
FC04
FC03, 06, 16

Table 15 Address ranges of Function Codes

8.2. Function Code 02 – Read Input Status
This function allows the control system to obtain the ON/OFF status of discrete inputs from
the MNS Digital Gateway. With function code 2 following information can be requested.
• Life Bits
• Status Information
• Control Access Information
• Alarms
• Trips
The valid address range: 10001-19999.
8.3. Function Code 03 – Read Holding Registers
With function code 03, the control system can read the registers that can store the numerical
data, which can be driven to external devices as mentioned below.
• Measuring Values
• Status as Word-oriented bits
• Alarm structure (Warnings/Trips)
The valid address range: 40001-49999
8.4. Function Code 04 – Read Input Registers
Function code 04 obtains the contents of the input registers. These locations receive their
values from devices connected to the I/O structure of field units and can only be referenced,
not altered within the system or via MODBUS as mentioned below.
Status as Word-oriented bits
Alarm structure (Warnings/Trips)
The valid address range: 30001-39999
40
Address / Mapping Area
10001-19999
30001-39999
40001-49999
FU N CT IO N CO D ES
Starting Address used in Modbus
Frame
0-9999
0-9999
0-9999
1TG C 9 0 8 0 0 4 M 0 2 0 1

Advertisement

Table of Contents
loading

This manual is also suitable for:

M10 seriesM102Mns digital