Connect The Pe Wire Of The Ac Input Cable; Connect The Ac Input Wires - ABB HVC 200 Operation And Installation Manual

Table of Contents

Advertisement

Installation
6.3.2

Connect the PE wire of the AC input cable

Preliminary requirements
Procedure
1. Prepare the wire:
a. Cut the PE wire (A) of the AC
b. Strip the insulation from the end
c. Attach the cable lug (C) to the end of the wire.
2. Attach the PE wire to the PE busbar. Use the fasteners (D).
3. Tighten the fasteners to the correct torque. For the specification, refer to
section 12.4.
6.3.3

Connect the AC input wires

Preliminary requirements
42
Wire stripper pliers
Wire cutter
Torque wrench
Cable lug
Fasteners M10
Bolts M10x20
input cable so that that the length
is sufficient for connection at the
PE busbar (B) below the terminal
block for the AC input.
Make sure the wire has a loop. The
loop is necessary so that the PE
wire is not the first wire that is
disconnected if a collision moves
the power cabinet.
of the wire. Make sure that the
stripped length is compatible with
the cable lug specification.
The front and right doors
are open.
Qualified installation
engineer
Wire stripper pliers, cable
lug tool and torque socket
wrench.
D
C
A
Cable lugs and fasteners.
Refer to section 12.13.3.
HVC 200/300/360-EN | 002
B