Fire-Lite Alarms MS-9200 Programming, Installation, Maintenance And Operating Instruction Manual page 98

Addressable control panel
Hide thumbs Also See for MS-9200:
Table of Contents

Advertisement

NFPA Standard-Specific Requirements
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This applications is not suitable for separate transmission of sprin-
kler supervisory or trouble conditions.
Notes:
3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
1.
Cut JP4 on the MS-9200 main circuit board to supervise placement of RTM-8F module and circuit.
2.
Refer to Figure 2-8, "Typical UL Power-limited Wiring Requirements," on page 27, and "UL Power-limited
3.
Wiring Requirements" on page 27, for information on UL power-limited wiring requirements.
FIGURE E-2:
Jumper JP2 must be in
position LE MUNCPL
BOX for use in this
application
Technical Manuals Online! - http://www.tech-man.com
Municipal Box Connected to RTM-8F Relay Transmitter Module
firealarmresources.com
Nonpower-limited
+
-
Transmitter Output
Document #15668
Rev. I
04/20/98
P/N 15668:I
FIRE
+
Municipal Box
-
Circuit
Gamewell Model
M34-56 Local Energy
Municipal Box
Polarities shown in
alarm condition
(Dummy load with a 1N4004
diode when no connection is
made)
95