Read Status
Read Status Entry
The operator presses the Enter key and the LCD display shows:
The operator presses '2' and the display shows:
From the display shown above, an operator may select one of the choices as listed below:
• To Display Point Status, the type of device to be read must first be identified by pressing the * key for a detec-
tor or the # key for a module. The two-digit device address is keyed in next, followed by the Enter key
• To Display Zone status, press the * key then press the * key a second time. Next, key-in the zone number (1 -
56) and press Enter. The Up and Down arrow keys are used to view the next or previous zone
• To Display System Parameters, press the * key then press the * key again followed by Enter
• To Display Bell Circuit status, press the * key, followed by the # key and then the digit '1' or '2', followed by
the Enter key
• To display the 500-event History file on the LCD, press the '1' key followed by the Enter key. The Up and
Down arrow keys are used to step through the entries in the file
• To Print Program Contents and Current System Status or History File, press the '2' and then the Enter key. A
new menu appears which prompts the user to press '1' to print Program/Status or '2' to print History file
During this and all subsequent operations except print operations, a two minute timer is started that will cause the
panel to return to the previous display if no key is pressed within two minutes. Each key press restarts the two minute
timer. A press of the left arrow (backspace) key deletes the previous entry. If there is no entry, it will cancel the Read
Status operation and return to the previous display. System Reset will also cancel the Read Status operation.
Display Point
Display Point operations display addressable device status on the LCD display. After the status of the device is dis-
played, the Up arrow key may be used to display the status of the next highest addressable device and the Down arrow
key may be used to display the status of the previous addressable device. The sequence of point display is Detector
points 01 - 99, Module points 01 - 99, NAC bell circuits 01 & 02, System Parameters and Zones 1 - 56.
A typical Read Status display is as follows:
Technical Manuals Online! - http://www.tech-man.com
 352*5$00,1*
 5'67$786 $&%$7
',63/$<32,17 $$
+,6725< 35,17 
1250$/602.('(73
:(67+$//:$<=
Document #15668
Rev. I
firealarmresources.com
04/20/98
P/N 15668:I
75

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200c

Table of Contents