Optional Modules; 1: Udact-F Universal Digital Alarm Communicator/Transmitter - Fire-Lite Alarms MS-9200 Programming, Installation, Maintenance And Operating Instruction Manual

Addressable control panel
Hide thumbs Also See for MS-9200:
Table of Contents

Advertisement

Optional Modules

2.15 Optional Modules
The MS-9200 supports option modules using connectors J6, J11 and J16 on the main circuit board. There are four
optional modules available for the MS-9200:
• RTM-8F Relay/transmitter Module
• PIM-24 Printer/PC Interface Module
• UDACT-F Universal Digital Alarm Communicator/Transmitter
• DIM-485 Display Interface Module (for use with LCD-40 Series annunciators)
Jumper JP4 must be cut before installation of the RTM-8F module to enable module placement supervision. Note
that devices connected to the standard EIA-485 connector, the optional EIA-232 connector, the optional EIA-485
connector via the PIM-24 or DIM-485 modules or SLC loop may be protected from voltage transients by using one of
the UL listed compatible surge suppressors listed in the Fire•Lite Device Compatibility Document.
Option Module Locations
FIGURE 2-28:
2.15.1 UDACT-F Universal Digital Alarm Communicator/Transmitter
The UDACT-F transmits system status to UL listed Central Station receivers via
the public switched telephone network. It is capable of reporting up to 56 soft-
ware zones or up to 198 addressable points. The UDACT-F may be mounted
directly to the MS-9200 main circuit board or remotely in a UBS-1F or ABS-8RF
enclosure. The MS-9200 requires software P/N 73580 or higher to support the
UDACT-F. For additional information, refer to the UDACT-F Manual.
46
Technical Manuals Online! - http://www.tech-man.com
Document #15668
Rev.I
firealarmresources.com
J11 accepts PIM-24 or DIM-485
J16 accepts UDACT-F
Cut JP4 for RTM-8F supervision
J6 accepts RTM-8F
FIGURE 2-29:
04/20/98
P/N 15668:I
UBS-1F

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200c

Table of Contents