The Control Module
Caution: Failure to break the tabs when configuring the module for Form-C operation can cause damage to the C304
!
module.
Communications Loop Connections
Connect the MS-9200 Communications SLC loop to C304 Terminals 1(-) and 2(+). The C304 occupies one module
address on the loop. Set the rotary switches on the module to the particular loop address required.
Contact Connections
Wire the common and the normally-open or normally closed contacts to the module as needed.
Contact Ratings
Resistive:
2 amps @ 30 VDC
Inductive:
1 amp @ 30 VDC (0.6 PF)
Pilot Duty:
0.6 amps @ 30 VDC (0.35 PF)
0.3 amps @ 110 VDC (0.35 PF)
0.3 amps @ 120 VAC (0.35 PF)
FIGURE 2-24:
MS-9200
Shield
A
B B+ A+ B- A-
T
B
1
2
3
6
SLC (+) TB6-3
SLC (-) TB6-5
1. Certain electromechanical devices exhibit inductive loading characteristics. For these types of devices, derate the outputs to 1
amp. Refer to the Device Compatibility Document for load characteristics by device.
42
Technical Manuals Online! - http://www.tech-man.com
1
C304 Control Module - Utilized as Form-C Relay
4
5
6
Normally-Open Contact
firealarmresources.com
+ To next device
- on Loop
+
-
-
-
+
C304
+
-
+
Break off Tabs
Document #15668
Rev.I
04/20/98
CAUTION! Do not loop wiring
under any terminals. Break wire
run to maintain supervision.
Common Contact
Normally-Closed Contact