Standard Relays; Notification Appliance Circuits - Fire-Lite Alarms MS-9200 Programming, Installation, Maintenance And Operating Instruction Manual

Addressable control panel
Hide thumbs Also See for MS-9200:
Table of Contents

Advertisement

Standard Relays

2.3
Standard Relays
The MS-9200 provides a set of Form-C alarm and Form-C trouble contacts rated for 2.0 amps @ 30 VDC (resistive).
The panel also provides a Form-A supervisory contact rated for 2.0 amps @ 30 VDC (resistive). Refer to Figure 2-4
for UL power-limited wiring requirements.
Note that relay connections may be power-limited or nonpower-limited, provided that 0.25" spacing is maintained
between conductors of power-limited and nonpower-limited circuits.
Relay Connections
FIGURE 2-6:
SUPV
NO C NO NC C NO NC C
1
TB3
2.4

Notification Appliance Circuits

The MS-9200 provides two Notification Appliance (bell) Circuits configurable for Style Y or Style Z. Each circuit is
capable of 2.5 amps of current. Total current drawn from these as well as other DC power outputs cannot exceed 6.0
amps. Use UL listed 24 volt notification appliances only. Circuits are supervised and power-limited. Refer to the
Fire•Lite Device Compatibility Document for a listing of compatible notification appliances. The two NACs (Notifi-
cation Appliance Circuits) located on the main circuit board may be expanded via the Fire•Lite FCPS-24F Field
Charger/Power Supply. Surge protection for notification appliances may be provided by using one of the UL listed
compatible surge suppressors listed in the Fire•Lite Device Compatibility Document.
NAC Connections
FIGURE 2-7:
Style Z Notification Appliance Circuit
(supervised and power-limited)
Polarized Bell
Polarized Strobe
Polarized Horn
Note: Notification Appliance
Circuit polarity shown in
alarm state.
26
Technical Manuals Online! - http://www.tech-man.com
ALARM
TROUBLE
2
3
4
5
6
7
8
+ -
+
B+
A+
A-
B-
T
B
2
firealarmresources.com
Power
Limited
Note: If relays are used as power-limited circuits,
paste supplied label to terminal block to indicate
use of power-limited wiring.
Style Y Notification Appliance Circuit (supervised and
power-limited - 4.7K ohm, ½ watt P/N 71252 UL listed)
+ -
Polarized Bell
+
Polarized Horn
+
Polarized Horn
B+
A+
A-
B-
T
Dummy Load all unused circuits
B
1
Document #15668
Rev.I
04/20/98
P/N 15668:I
If using both power-limited and
nonpower-limited circuits,
leave one unused terminal
between power-limited and
nonpower-limited circuits.
Power
Limited

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200c

Table of Contents