Wiring Detectors

2.14 Wiring Detectors
To install addressable detectors:
Connect the MS-9200 Communications SLC loop to Terminal (-) and (+) on the removable terminal block.
1.
If an RA400Z Remote LED Annunciator is being employed, connect the RA400Z positive terminal to the
2.
RA+ terminal on the removable terminal block and the negative terminal to the RA(-) terminal on the remov-
able block.
Before installing the appropriate addressable detector head, set the detector's address on the head with a small
3.
flathead screwdriver. Mark this address on the head.
Place the removable terminal block into the connector in the detector head. Be certain to properly align and
4.
snap-in securely.
FIGURE 2-27:
Channel (+)
Channel (-)
Technical Manuals Online! - http://www.tech-man.com
Wiring Detector with Removable Plug-in Connector
Communications
SLC Loop
COMM
SD300 with removable
plug-in connector
firealarmresources.com
Document #15668
Rev. I
04/20/98
P/N 15668:I
Channel (+)
to next device
on Loop
Channel (-)
RA400Z Remote LED
Annunciator
45