Fire-Lite Alarms MS-9200 Programming, Installation, Maintenance And Operating Instruction Manual page 40

Addressable control panel
Hide thumbs Also See for MS-9200:
Table of Contents

Advertisement

The M302 Monitor Module
Style B Initiating Device Circuit (Utilizing M300)
The NFPA Style B IDC (Initiating Device Circuit), utilizing an M300 Monitor Module, is supervised and
power-limited.
FIGURE 2-19:
Resettable 24 VDC
4-wire smoke
detector power
(300 mA max.)
+
-
T
B
1
2
4
24V (+) TB4-5
24V (-) TB4-6
Technical Manuals Online! - http://www.tech-man.com
Style B Circuit using M300
To Next Device on Loop
+
+
- +
-
3
4
5
6
firealarmresources.com
End-of-Line Resistor
47K ohm, ½ watt resistor
(N-ELR in Canada)
24 VDC 4-Wire Smoke Detector
Manual Pull
Station
-
Heat Detector
-
-
+
+
+
-
M300
MS-9200
Document #15668
Rev. I
04/20/98
P/N 15668:I
UL listed Power Supervision Relay
(must be wired as last device on
loop as shown).
-
+
+
-
+
+
-
+
-
+
-
+
-
+
CAUTION! Do not loop wiring
under any terminals. Break wire
run to maintain supervision.
Loop Out
Shield
A
B B+ A+ B- A-
T
B
1
2
3
4
5
6
SLC (+) TB6-3
SLC (-) TB6-5
-
-
6
37