Fire-Lite Alarms MS-9200 Programming, Installation, Maintenance And Operating Instruction Manual page 43

Addressable control panel
Hide thumbs Also See for MS-9200:
Table of Contents

Advertisement

The M302 Monitor Module
Style D Initiating Device Circuit (Utilizing M302 Monitor Module)
The NFPA Style D IDC (Initiating Device Circuit) is supervised and power-limited.
FIGURE 2-22:
Resettable 24 VDC
4-wire smoke
detector power
(300 mA max.)
+
- +
T
B
1
2
4
24V (+) TB4-5
24V (-) TB4-6
40
Technical Manuals Online! - http://www.tech-man.com
Style D Circuit using M302
To Next Device
on Loop
+
- +
-
3
4
5
6
firealarmresources.com
End-of-Line
Resistor
-
3.9K ohm
(included)
CAUTION! Do not loop wiring
under any terminals. Break wire
run to maintain supervision.
M302
MS-9200
Document #15668
Rev.I
04/20/98
P/N 15668:I
-
+
-
+
UL listed
Compatible
Smoke
Detector
-
+
-
+
UL listed
Compatible
Smoke
Detector
-
+
-
+
UL listed
Compatible
Smoke
Detector
Loop Out
Shield
A
B B+ A+ B- A-
T
B
1
2
3
4
5
6
6
SLC (+) TB6-3
SLC (-) TB6-5