Appendix D: Afm And Ldm Series Wiring - Fire-Lite Alarms MS-9200 Programming, Installation, Maintenance And Operating Instruction Manual

Addressable control panel
Hide thumbs Also See for MS-9200:
Table of Contents

Advertisement

AFM and LDM Series Wiring
Appendix D
The following illustrations show the various configurations which may be wired utilizing AFM Series Annunciators.
LDM Series Annunciators may be used in a similar manner. All illustrations show power supplied to annunciators by
the MS-9200. For system applications requiring greater than the 300 mA of nonresettable power the MS-9200 can
supply, use the Fire•Lite FCPS-24F Field Charger Power Supply.
The following figure shows a configuration which provides 56 zones of alarm and trouble indications, remote
Acknowledge/Step, Alarm Silence, Drill and System Reset keys, System Supervisory, AC Fail, and Trouble indica-
tions. Use AKS-1F keyswitch to prevent unauthorized actuation of control switches. Refer to the AFM Manual for
further details.
AFM-16ATX
8 Zones (Alarm & Trouble)
4 switches IACK, SIL,
DRILL, RESET), System
Trouble LED, On-Line/Off-
Line Power LED, Piezo
sounder
Annunciator Power - 12 to 18 AWG
Technical Manuals Online! - http://www.tech-man.com
AFM and LDM Series Wiring
AEM-16ATF
Ribbon
Cable
16 Zone (Alarm & Trouble)
2-wire EIA-485 circuit -
max. 6,000 ft. @ 16 AWG
Data Communication Port:
EIA-485 @ 20K Baud
MS-9200
Document #15668
firealarmresources.com
AEM-16ATF
Ribbon
Cable
16 Zone (Alarm & Trouble)
Ribbon
Ribbon
Cable
Cable
Rev. I
04/20/98
P/N 15668:I
AEM-16ATF
Ribbon
Cable
16 Zone (Alarm & Trouble)
Ribbon
Cable
89