The Control Module
NFPA Style Y Notification Appliance Circuit (Utilizing C304 Module)
All circuits are supervised and power-limited.
FIGURE 2-25:
+
- +
T
B
1
2
4
24V (+) TB4-1
24V (-) TB4-2
Technical Manuals Online! - http://www.tech-man.com
Style Y NAC using C304
End-of-Line Resistor 47K ohm, ½ watt resistor
(N-ELR in Canada)
Note: If more than one C304 NAC is provided,
install the power supervision relay after the last
notification appliance.
To Next Device on Loop
+
- +
-
3
4
5
6
firealarmresources.com
24 VDC Notification Appliance
24 VDC Notification Appliance
-
24 VDC Notification Appliance
+
-
-
-
+
+
3
-
CAUTION! Do not loop wiring
4
+
under any terminals. Break wire
run to maintain supervision.
C304
MS-9200
Resettable 24 VDC
4-wire smoke
detector power
(300 mA max.)
Document #15668
Rev. I
04/20/98
P/N 15668:I
UL listed Power Supervision Relay
(must be wired as last device on
loop as shown).
-
+
-
+
-
+
-
+
-
+
-
+