NFPA Standard-Specific Requirements
NFPA Signaling Systems for Central Station Service (Protected Premises Unit)
The following figure illustrates an example of Central Station Reporting using an MS-5012. The relay contacts from
the MS-9200 may be used to trip any dialer UL listed for Central Station Services. The UDACT-F may also be used.
Refer to Figure 2-31, "UDACT-F Mounting to MS-9200," on page 47 and Figure 2-32, "External UDACT-F Mount-
ing in ABS-8RF," on page 48, for information on installation.
Notes:
Reference the MS-5012 Manual for additional information
1.
Program the MS-5012 for slave operation
2.
SW2 Trouble/No AC switch located on the bottom right of the MS-9200 main circuit board, must be posi-
3.
tioned in the down position for this application. This prevents the transmission of a trouble on the loss of AC
power
FIGURE E-1:
94
Technical Manuals Online! - http://www.tech-man.com
Central Station Service Using MS-5012
MS-5012
Phone Line
Transformer
AC wiring for DACT/FACP must be
connected to the same branch circuit.
MS-5012 Connections to MS-9200
TABLE E-1:
Alarm
Trouble
Supervisory
firealarmresources.com
MS-9200
MS-5012
MS-9200
TB2-1
TB3-5
TB2-2
TB3-3
TB2-3
TB3-8
TB2-4
TB3-6
TB2-9
TB3-2
TB2-10
TB3-1
Document #15668
Rev.I
04/20/98
P/N 15668:I
Alarm
Trouble
Supv.
ELR = 2.2K ohms (supplied with MS-5012)