Fire-Lite Alarms MS-9200 Programming, Installation, Maintenance And Operating Instruction Manual page 42

Addressable control panel
Hide thumbs Also See for MS-9200:
Table of Contents

Advertisement

The M302 Monitor Module
Style B Initiating Device Circuit (Utilizing M302 Monitor Module)
The NFPA Style B IDC (Initiating Device Circuit) is supervised and power-limited.
FIGURE 2-21:
Resettable 24 VDC
4-wire smoke
detector power
(300 mA max.)
+
- +
T
B
1
2
4
24V (+) TB4-5
24V (-) TB4-6
Technical Manuals Online! - http://www.tech-man.com
Style B Circuit using M302
To Next Device on Loop
+
- +
-
3
4
5
6
firealarmresources.com
UL listed Compatible
Smoke Detector
UL listed Compatible
Smoke Detector
-
UL listed Compatible
Smoke Detector
-
-
+
+
+
-
-
3
CAUTION! Do not loop wiring
+
4
under any terminals. Break wire
run to maintain supervision.
M302
MS-9200
Document #15668
Rev. I
04/20/98
P/N 15668:I
End-of-Line Resistor
3.9K ohm (included)
-
+
-
+
-
+
-
+
-
+
-
+
Loop Out
Shield
A
B B+ A+ B- A-
T
B
1
2
3
4
5
6
6
SLC (+) TB6-3
SLC (-) TB6-5
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200c

Table of Contents