Program Change - Level One
There are nine system function options for software P/N 73750 or greater. The factory default selections and user
option selections are shown below:
FUNCTION
V = Alarm Verification
I = Silence Inhibit
A = Autosilence
P = Presignal
C = Bell Code
A/U = Annunciators
with or without UDACT-F
L/P = LCD-40 or
Printer/PC in use
S = SLC loop style
R = Alarm/Trbl Reminder
1Requires prior approval of Local Authority Having Jurisdiction.
2When the UDACT-F has a fault, this entry allows the FACP to display 'DACT Trouble' on the LCD display and printer hardcopy. The history
file will also be updated with this information. For zone annunciation, up to 56 zones, use AFM Series Annunciators or LDM Series Annunci-
ators. For 198 point annunciation, use the LDM Series Annunciators.
3.3.5 Password Change
While displaying the Program Menu, press '4' to change either of two passwords. One high level password, defaulted
to '00000', allows for point and system programming. A second lower level password, defaulted to '11111', allows for
status changes such as:
• Disable points/zones
• Clear history file
• Walktest enable
• Time and date set
• Program check
Pressing '4' will display the following:
Select the password to change by typing * or #, then enter the new password. As the new program or status password
is entered, it is displayed. When ENTER is pressed, the display reads 'PRESS ENTER IF OK, NNNNN=NEW PRO-
GRAM PW'. After ENTER is pressed, the new password is stored in EEPROM memory and the program returns to
62
Technical Manuals Online! - http://www.tech-man.com
DEFAULT
SELECTION
(N)one
(Y) 120 seconds
(N)one
(Y) 60 seconds
(N)one
(Y) 10 minutes
(N)one
(Y) 3 minutes with 15 second Acknowledge
(N)one
(M) = March Time
(T) = Temporal
(C) = California
(N)one
(Z) = 56 Zones
(ZU) = 56 Zones Annunciator with UDACT-F
(P) = 198 Points
(PU) = 198 Points Annunciator with UDACT-F
(N)one
L = LCD-40 Series installed (requires DIM-485)
P = Printer or local PC installed (requires PIM-24)
(4) = Style 4
(6) = Style 6
(N)o
(Y)es = Sound onboard piezo every 15 seconds
11111( /(9(/3:
11111( /(9(/3:
Document #15668
firealarmresources.com
1
1
during alarm and every two minutes during
trouble after acknowledge or silence key
has been pressed.
Rev.I
04/20/98
P/N 15668:I