Fire-Lite Alarms MS-9200 Programming, Installation, Maintenance And Operating Instruction Manual page 83

Addressable control panel
Hide thumbs Also See for MS-9200:
Table of Contents

Advertisement

Power Supply Calculations
Battery Calculations
TABLE A-4:
Standby Load
Current (amps)
[
]
Alarm Load
Current (amps)
[
]
Add Standby and Alarm Load for Required Ampere Hour Battery
Notes:
Up to 7 AH batteries can be located in the older MS-9200 backbox, up to 12 AH batteries can be located in the
1.
newer MS-9200 backbox
12 AH (older backbox) to 18 AH (older and newer backbox) batteries require the Fire•Lite BB-17F battery
2.
box
When new MS-9200 main circuit board is installed (allows disabling of FACP battery charger), the
3.
CHG-120F Battery Charger for 25 AH to 100 AH batteries (requires separate housing)
80
Technical Manuals Online! - http://www.tech-man.com
Required Standby Time in Hours
X
Required Alarm Time in Hours
X
Multiply by the Derating Factor or 1.2
Total Ampere Hours (AH) Required
firealarmresources.com
(24 or 60 Hours)
[
]
(i.e. 5 minutes = 0.084)
[
]
Document #15668
Rev.I
04/20/98
P/N 15668:I
=
__________
=
__________
=
__________
X 1.2
__________
=
__________

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200c

Table of Contents