4098-9822 Relay Module Wiring - Simplex 4098 Applications Manual

Detectors, sensors, and bases
Hide thumbs Also See for 4098:
Table of Contents

Advertisement

Relay Module Accessories,
4098-9822 Relay
The 4098-9822 Relay Module is used with the 4098-9789, -9791, -9794, -9795, and -9796
Module Wiring
Sensor Bases. Install the relay module using Figure 3-7 and the figure below as a reference.
IMPORTANT: Do not use a remote LED if using the 4098-9822 relay module.
FigureTag FD4-709-10
Notes:
1. Do not use remote LED.
2. 18 to 32 VDC, .008 amps typical / .013 amps. Maximum.
3. Contact A or B: Dry, Form "C" - each rated 2 amps resistive at 24 VDC/0.5 amps at
Continued
The 4098-9822 relay module is not supervised and should only be
used for non-critical supplementary functions. There is a limit of
ten control outputs activated on a MAPNET II/IDNet channel. If the
channel capacity is exceeded, the relay module may not function
properly.
+ 2 4 V D C
F R O M
P A N E L
0 V
(IF U S E D )
(S E E N O T E 2 )
C E N T E R
C O N T A C T B
N .C .
(S E E N O T E 3 )
N .O .
Figure 4-2. 4098-9822 Relay Module Wiring
110 VAC, resistive.
firealarmresources.com
+ 2 4 V D C
T O O T H E R 2 4 V D C
D E V IC E S O R
0 V
S U P E R V IS O R Y M O D U L E
(S E E N O T E 1 )
W H IT E
B L U E
R E D
R E D
4 0 9 8 -9 8 2 2
From 4098-9789, -9791, -9794,-9795, -9796
R E L A Y
Sensor Base
B L A C K
B L A C K
B R O W N
O R A N G E
V IO L E T
Y E L L O W
G R E Y
G R E E N
4-3
-B L U E
+ W H IT E
C E N T E R
C O N T A C T A
N .C .
(S E E N O T E 3 )
N .O .
Continued on next page