Simplex 4098 Applications Manual page 51

Detectors, sensors, and bases
Hide thumbs Also See for 4098:
Table of Contents

Advertisement

Compatibility,
Continued
Compatibility for
4098 Detectors and
Detector Bases
Notes:
1.
For detailed interconnection data,
see wiring diagrams for specific
panels.
2. Panel compatibility identification
marker is model number of the
module or panel.
3. Sensor compatibility identification
marker is model number found
on sensor label.
4. 4098-9754 sensor NOT compatible
with bases that have a RED DOT
located in sensor mounting area.
5. Maximum quantity of 4098-9794
Sounder Bases, 4098-9795
Multi-Sensor Sounder Bases, and CO
Sounder bases (4098-9798) when
output is coded via MAPNET II/IDNet
control (Temporal Code) is 43.
If coding is performed via 24 VDC or
NAC circuit, use limits specified in
Table 5-2.
This section describes the compatibility between FACPs, sensors, and sensor bases.
Table 5-2. 4098 Sensor and Sensor Base Compatibility
Sensors
4098-9714
4098-9717
4098-9733
4098-9714
4098-9717
4098-9733
4098-9714
4098-9717
4098-9733
4098-9714
4098-9733
4098-9714
4098-9717
4098-9733
4098-9754
4098-9754
4098-9757
4098-9746
firealarmresources.com
Compatible Bases
4098-9789
4098-9791
4098-9792
4098-9789
4098-9792
4098-9789
4098-9791
4098-9792
4098-9793
4098-9797 (4100U/4100ES
only)
4098-9789
4098-9791
4098-9792
4098-9793
4098-9794
(See Note 5)
4098-9798
(See Note 5)
(4100U/4100ES, IDNet only)
4098-9795
(See Note 5)
4098-9796
4098-9792
4098-9789
4098-9791
4098-9794
(See Note 5)
4098-9797
4098-9798
(See Note 5)
4098-9788
4098-9797
4098-9798
(See Note 5)
5-3
Max. Quantity of Devices Per Circuit
MAPNET II:
127 (4020), 127 (4100+)
127 (4120), 127 (4100U), 127 (4100ES)
Addresses 1-127
128 (CDT TrueAlarm)
Addresses 0-127
IDNET:
250 (4010), 250 (4100U), 250 (4100ES)
Addresses 1-250
IDNET:
200 (4008)
Addresses 1-200
MAPNET II:
127 (4020), 127 (4100+)
127 (4100U), 127 (4100ES), 127 (4120)
Addresses 1-127
IDNET:
250 (4010), 250(4100U), 250 (4100ES)
Addresses 1-250
MAPNET II:
63 (4020, 4100+, 4100U, 4100ES, 4120)
Addresses 2 to 126
IDNET:
124 (4010), 124 (4100U), 124 (4100ES)
Addresses 2 to 248
IDNET:
250 (4100U), 250 (4100ES)
Addresses 1-250
IDNET:
250 (4100U/4100ES with 4100-3106)
250 (4010)
Addresses 1-250
IDNET:
250 (4100U), 250 (4100ES)
Addresses 1-250

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 4098 and is the answer not in the manual?

Questions and answers

Table of Contents

Save PDF