Special Considerations

Overview

Before installing detectors/sensors, make a survey of the area to be covered in accordance with
information provided in NFPA 72, (an excerpt of which is provided in the "Smoke Detector/
Sensor Applications" section below). For additional information, refer to NFPA 72 and the
NEMA Guide for Proper Use of System Smoke Detectors.
Special
Considerations for
Smoke Detectors
and Sensors
Smoke
Each detector/sensor is capable of providing up to 900 square feet (84 square meters) of coverage,
Detector/Sensor
depending on the following:
Applications
Is there human occupancy?
Contents to be protected.
Type of construction and use.
Burning characteristics of contents.
Air movement - stratification.
Deflections and obstructions.
Height of ceilings.
Surface conditions of ceilings.
Type of ceiling construction.
Total area.
Vent locations - velocities - dilution.
Requirements of local codes.
Results of engineering evaluation.