4098 Truealarm Sensors; Specifications; Special Applications; Mounting - Simplex 4098 Applications Manual

Detectors, sensors, and bases
Hide thumbs Also See for 4098:
Table of Contents

Advertisement

4098 TrueAlarm Sensors

Specifications

Sensor PID
Type of Sensor
Average
Operating
Current
UL Temperature
Rating*
Humidity Range
(Non-Condensing)
Air Velocity
Range
*
Fixed temperature functions are software programmed and selectable from the UL temperature rating.
**
UL Max. Ambient Ceiling Temp. of 100° F (38° C) at 3600 sq. ft of Max. Coverage.
UL Max. Ambient Ceiling Temp. of 100° F (38° C) at 1600 sq. ft of Max. Coverage.

Special Applications

1. Smoke sensor sensitivities are set and continuously monitored by the control unit.
2. The 0.2%/FT, 0.5%/FT, and 1.0%/FT settings for the 4098-9714 and 4098-9754 sensor and the
3. To determine if an area is suitable for the 0.2%/FT setting, set the sensitivity for the installed
4. To determine if an area is suitable for the 0.5%/FT setting, set the sensitivity for the installed
5. To determine if an area is suitable for the 0.9%/FT or 1.0%/FT setting, set the sensitivity for
All sensors identified in Table 3-2 mount to a sensor base (refer to the "4098 TrueAlarm

Mounting

Sensor Bases" section of this chapter for more information). Use the following information and
Figure 2-1 when mounting TrueAlarm sensors.
Table 3-2. TrueAlarm Sensor Specifications
4098-9714
4098-
9717
Photoelectric
Ionizat
ion
80 A
80 A
10-
10-95% RH
95%
RH
0-200
0-2000 FPM
FPM
The sensitivity range (setting) for the 4098-9714 and 4098-9754 sensor is 0.2%/FT to
3.7%/FT smoke obscuration. The sensitivity range (setting) for 4098-9717 sensors is
0.5%/FT to 1.3%/FT.
0.5%/FT and 0.9%/FT settings for the 4098-9717 sensor are for special applications only.
The 0.2%/FT, 0.5%/FT, 0.9%/FT, and 1.0%/FT settings are very sensitive settings: only use the
0.2%/FT setting when a sensor is located in a totally smoke-free and controlled
temperature environment, such as a computer room or telephone switching exchange.
sensor at 1.5%/FT and monitor the peak values for 90 days. If you record a peak value of
0.1%FT or higher during the 90 days, do not use the 0.2%/FT setting.
sensor at 1.5%/FT and monitor the peak values for 90 days. If you record a peak value of
0.25%FT or higher during the 90 days, do not use the 0.5%/FT setting.
the installed sensor at 1.3%/FT (Ion) 1.5/FT (Photo) and monitor the peak values for
90 days. If you record a peak value of 0.5% or higher during the 90 days, do not use the
0.9%/FT (Ion) or 1.0%/FT (Photo) settings.
firealarmresources.com
4098-9733
Heat
6 A at 68 F (20°C)
13 A at 135 F (57 C)
135 F (57 C)**
155 F (68 C)†
10-95% RH
3-2
4098-9754
4098-9746
Photo/Heat
Gas
90 A
50µA
135 F (57 C)**
155 F (68 C)†
15-95% RH
(15-90% for
10-95% RH
long term
exposure)
0-2000 FPM
0-1000 FPM