Multi-Sensor Bases 4098-9795 And 4098-9796; Wiring - Simplex 4098 Applications Manual

Detectors, sensors, and bases
Hide thumbs Also See for 4098:
Table of Contents

Advertisement

4098 TrueAlarm Sensor Bases,
Multi-Sensor Bases
The 4098-9795 and 4098-9796 Multi-Sensor Bases are only for use with the 4098-9754
4098-9795 and
multi-sensor and are not compatible with the 2120 CDT. Both bases have remote LED output and
4098-9796
the 4098-9795 also has an integrated sounder similar to the 4098-9794 Sounder Base. The
4098-9795 and 4098-9796 Multi-Sensor Bases must be used with the 4098-9754 multi-sensor
when connected to a 4010, 4020, 4100+, 4008, or 4120 system. When connected to a 4100U or a
4100ES the 4098-9754 multi-sensor can also be used with the 4098-9789, -9791, -9792, -9793, -
9794, -9797, and -9798 bases.
The Multi-Sensor Base answers to two addresses, therefore the DIP Switch must be set for
even addresses only. The even address is a photo sensor/sounder base (4098-9795) or a photo
sensor/standard base (4098-9796), and the odd address (DIP Switch + 1) is a heat sensor/standard
base. The figure below shows the allowable addresses for the Multi-Sensor Bases.
IMPORTANT: Switch Position 1 is not used and must always be OFF (0) for the
LSB
SEE
NOTE 1
ON
OFF
RESERVED FOR
FUTURE USE
DIP
SWITCHES
1 THRU 4
Note: The 4098-9795 Multi-Sensor Sounder Base has a 9-position DIP Switch that is used for

Wiring

Sensor bases are connected to the fire alarm control panel via a single wire pair for the 4098-9789,
-9792, -9793, -9796, and -9797 and two pairs of wires for the 4098-9791, -9794, -9795, and -9798.
Using Figure 3-7 as a reference, connect the bases to the MAPNET II/IDNet wire pair and 24V
power
(if used).
IMPORTANT: For additions to existing installations, remove power from the panel
Continued
Multi-Sensor Bases to function properly. The odd address immediately
after the DIP Switch setting must not be used by any other sensor base or
MAPNET/IDNet device.
MSB
1
2
3
4
5
6
7
8
9
SEE
NOTE
0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111
0000
0
16
32
48
2
18
34
50
0100
0010
4
20
36
52
0110
6
22
38
54
8
24
40
56
0001
10
26
42
58
0101
0011
12
28
44
60
0111
14
30
46
62
SWITCH 1 MUST BE SET TO OFF
FOR PROPER OPERATION
Figure 3-6. 4098-9795, -9796, 9798 Multi-Sensor Base DIP Switch Address Settings
setting base address and selecting the sounder power source. See Figure 3-2 for DIP Switch
location.
before wiring any bases to avoid damage to equipment.
firealarmresources.com
DIPSWITCH IS SHOWN
SET AT ADDRESS 4.
1 = ON
0 = OFF
DIP SWITCHES 5 THRU 8
64
80
96
112
128
144
66
82
98
114
130
146
68
84
100
116
132
148
70
86
102
118
134
150
72
88
104
120
136
152
74
90
106
122
138
154
76
92
108
124
140
156
78
94
110
126
142
158
3-7
160
176
192
208
224
240
162
178
194
210
226
242
164
180
196
212
228
244
166
182
198
214
230
246
168
184
200
216
232
248
170
186
202
218
234
250
172
188
204
220
236
252
174
190
206
222
238
254
RESERVED FOR FUTURE USE