4.4.4 Remote EPO

● Prepare the EPO switch and cable before installation. The recommended cable
● Equip the EPO switch with a protective cover to prevent misoperations, and
Connect the EPO button to the EPO port on the SmartLi using the cable.
Figure 4-44 Cable connection for an NO EPO switch
Figure 4-45 Cable connection for an NC EPO switch

4.4.5 Installing Output Cables

Issue 09 (2022-01-30)
NO TICE
size is 22 AWG.
cover the cable with protective tubing.
NO TE
● When the EPO switch is in the NC state, remove the jumper between EPO_NC and
EPO_12V before connection. When the EPO switch is turned off, EPO is triggered.
● When the EPO switch is in the NO state, ensure that the jumper is connected between
EPO_NC and EPO_12V. When the EPO switch is turned on, EPO is triggered.