Item
Cell
undervoltage
protection
threshold
Battery
undervoltage
protection time
(h)
Table 6-3 Alarm Settings
Item
Battery cabinet
EPO
Copper bar
overtemperature
Fire extinguisher
cylinder pressure
abnormal
Battery
overcurrent
(discharge)
Issue 09 (2022-01-30)
Description
You can adjust the EOD
threshold as required.
Maximum battery discharge
time.
Description
Emergency power-off
(EPO) is performed only
when this parameter is set
to Enable and the EPO
switch is triggered.
When the value is changed
from Disable to Enable,
check that the EPO cable is
connected correctly.
If this parameter is set to
Enable, an alarm is
reported when the copper
bar is overheated.
If this parameter is set to
Enable, an alarm is
reported when the fire
extinguisher cylinder
pressure is abnormal.
If this parameter is set to
Disable, no alarm is
reported when battery
overcurrent occurs during
discharging.
If this parameter is set to
Enable, an alarm is
reported when battery
overcurrent occurs during
discharging.
Copyright © Huawei Technologies Co., Ltd.
6 Operations
Default
Value Range
Value
2.5
2.5–2.9
48
24~3000
Default
Value Range
Value
Disable
Disable, Enable
Enable
Disable, Enable
Enable
Disable, Enable
Disable
Disable, Enable
112