Huawei SmartLi 2.0 User Manual page 113

Hide thumbs Also See for SmartLi 2.0:
Table of Contents

Advertisement

SmartLi 2.0
User Manual
Item
DO_2
DO_2 Action
Table 5-15 Alarm Settings
Item
Battery cabinet
EPO
Copper bar
overtemperature
Fire extinguisher
cylinder pressure
abnormal
Battery
overcurrent
(discharge)
Issue 09 (2022-01-30)
Description
Output dry
contact 2 function
setting for the
lithium battery
cabinet
Output dry
contact 2 action
setting for the
lithium battery
cabinet
Description
Emergency power-off (EPO) is
performed only when this
parameter is set to Enable and
the EPO switch is triggered.
When the value is changed from
Disable to Enable, check that the
EPO cable is connected correctly.
If this parameter is set to Enable,
an alarm is reported when the
copper bar is overheated.
If this parameter is set to Enable,
an alarm is reported when the fire
extinguisher cylinder pressure is
abnormal.
If this parameter is set to Disable,
no alarm is reported when battery
overcurrent occurs during
discharging.
If this parameter is set to Enable,
an alarm is reported when battery
overcurrent occurs during
discharging.
Copyright © Huawei Technologies Co., Ltd.
Default Value
None
Close
Default
Value
Disable
Enable
Enable
Disable
5 User Interface
Value Range
● None
● Critical alarm
● Minor alarm
● Fire
extinguishing
started
● Battery temp.
abnormal
● Battery EOD
● Battery
undervoltage
● Close
● Open
Value
Range
Disable,
Enable
Disable,
Enable
Disable,
Enable
Disable,
Enable
103