Table 5-10 System Settings
Item
Battery cabinet
quantity
Charging mode
Cell
undervoltage
protection
threshold (V)
Battery
undervoltage
protection time
(h)
Table 5-11 Settings Wizard
Item
Language
Time
Network Param.
System Param.
Issue 09 (2022-01-30)
NO TE
● After you restart the device, IP address allocation changes back to Manual. The IP
address is set to the IP address set previously.
● Ensure that the UPS IP address is unique on the network segment. Otherwise, the
WebUI display function may not function properly.
Description
Specifies the number of
battery cabinets connected in
parallel.
Mode 1 can meet the
requirements of most
customers.
Mode 2 meets the
requirements for charging
batteries immediately after
discharging is complete at a
high temperature.
You can adjust the EOD
threshold as required.
Maximum battery discharge
time.
Description
English, Chinese
Date format, YYYY-MM-DD, time zone,
city, and time
IP address allocation, IP address,
subnet mask, and gateway
Battery cabinet quantity, charging
mode, cell undervoltage protection
threshold, and battery undervoltage
protection time
Copyright © Huawei Technologies Co., Ltd.
5 User Interface
Default
Value Range
Value
1
1–15
Mode 1
Mode 1, Mode 2
2.5
2.5–2.9
48
24~3000
Remarks
Set based on site
requirements.
Set based on site
requirements.
Set based on site
requirements.
Set based on site
requirements.
100