Step 8 Connect the dry contact cable to the fire extinguisher cylinder.
Step 9 Observe the pressure gauge on the front of the cabinet. The value of the pressure
gauge should be within the allowable pressure range (1.6–1.8 MPa at 20°C)
specified in
8 hours, observe the pressure gauge again. The position should remain
unchanged.
Step 10 Press and hold the POWER ON/OFF button on the BCU for more than 2s. The
green indicator of the BCU blinks at 4 Hz.
Step 11 After the green indicator of the BCU blinks at 10 Hz and the red indicator is steady
on, switch on the battery circuit breaker on the SmartLi.
----End
Issue 09 (2022-01-30)
Table
4-3, and record the position of the pressure gauge pointer. After
Copyright © Huawei Technologies Co., Ltd.
9 Parts Replacement
154