Table 69 General Alarms - WAGO 765-1202/0100-0000 Product Manual

I/o system field 16-channel digital input/output; ethercat; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

Diagnostics
Emergency Error Code (hex)
22xx
23xx
30xx
31xx
32xx
33xx
40xx
41xx
42xx
50xx
60xx
61xx
62xx
63xx
70xx
80xx
81xx
8110
8120
8130
8140
8150
82xx
8210
8220
90xx
F0xx
FFxx
The following device-specific emergency error codes are used by the device (diagnostic
type: warning):
Emergency
Error Code
(hex)
0xFF00
0xFF01
0xFF02
0xFF03
0xFF04
86
Product manual | Version: 1.0.0
16DIO FLD EC DC 24V 2.0A
Description
Current inside the device
Current, device output side
Voltage
Mains Voltage
Voltage inside the device
Output Voltage
Temperature
Ambient Temperature
Device Temperature
Device Hardware
Device Software
Internal Software
User Softwares
Data Set
Additional Module
Monitoring
Communication
CAN Overrun (Objects lost)
CAN in Error Passive Mode
Life Guard Error or Heartbeat Error
recovered from bus off
Transmit COB-ID
Protocol Error
PDO not processed due to length error
PDO length exceeded
External Error
Additional Functions
Device-specific
Alarm
Description
Undervoltage
Undervoltage in supply line 1L
The supply line has fallen below the limiting
value for the minimum voltage.
Overvoltage
Overvoltage in supply line 1L
The supply line has exceeded the limiting
value for the maximum voltage.
Overtempera-
Overtemperature
ture
The device temperature has exceeded the
upper limiting value.
Overload
Overload in supply line 1L
The total current in supply line 1L has ex-
ceeded the upper limiting value.
Overload, 2L
Overload in supply line 2L
765-1202/0100-0000
Table 69: General Alarms
Remedy
Check supply voltage
Check supply voltage
Eliminate external heat source
or overload.
Eliminate overload.
Eliminate overload.

Advertisement

Table of Contents
loading