Mechanical Data; Connection Technology; Table 9 Mechanical Data; Table 10 Connection Technology - WAGO 765-1202/0100-0000 Product Manual

I/o system field 16-channel digital input/output; ethercat; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

Properties

4.4.2 Mechanical Data

Property
Width
Height
Length
Weight
Housing
Mounting type
Tightening torque
Mounting holes

4.4.3 Connection Technology

Property
Power Connection
EtherCAT Connection
Digital inputs/outputs
Tightening Torque
Digital Input/Output, 1L or 2L Powered
Property
Digital Input
Characteristic
Parameters
Recording cycle
Circuit
Indicators
Digital Output
Output voltage
Current
Residual current
18
Product manual | Version: 1.0.0
16DIO FLD EC DC 24V 2.0A
Table 9: Mechanical Data
Value
60 mm
30 mm
210 mm
610 g
Zinc Die Casting
Screw mount, 2 × M4
M4: 1.2 Nm
Diameter: 4.5 mm
Distance from each: 198.0 mm ± 0.2 mm
Table 10: Connection technology
Value
PWR IN: M12 L-coded, 5-pin, plug
PWR OUT: M12 L-coded, 5-pin, socket
2 × M12, D-coded, socket, 4-pin
8 × M12, A-coded, socket, 5-pin
M12: 1.0 Nm
Table 11: Digital Input/Output, 1L or 2L Powered
Value
Type 3 (IEC 61131-2)
Digital software input filter: without, 3 ms ... 20 ms
The input signal change must be at most 2.5 kHz for
correct device-internal detection of changes. However,
it should be noted that the transfer and processing of
the process data (in the device and in the controller)
also take time and reduce the maximum input signal
change.
200 μs
The digital input is not resistant to reverse power feed-
ing.
The input voltage must not exceed the supply voltage.
On/off status LED
24 VDC
Port X01 to X04: 1L powered
Port X05 to X08: 2L powered
Normal operation: max. 2.0 A per channel
Overload operation: max. 2.4 A per channel, per
IEC 61131-2
Less than 1 mA
765-1202/0100-0000

Advertisement

Table of Contents
loading