Analog Output; Signal Type; Value To Be Output; Signal Range Start Value - JUMO IPC 300 Operating Manual

Electronic transformer
Hide thumbs Also See for IPC 300:
Table of Contents

Advertisement

5 Configuration
5.1.9

Analog output

Signal type

Value to be output

Signal range start
value
Signal range end
value

5.1.10 RS422/485

Baud rate

Data format

Device address

60
Different internal values can be output as a standard signal at the analog out-
put.
Value / settings
Switched off
0 to 20 mA
4 to 20 mA
0 to 10 V
2 to 10 V
0 to 5 V
1 to 5 V
Load voltage
2
Load voltage
Load current
2
Load current
Power (in W)
Power (in kW)
Load resistance
DC intermediate cir-
cuit voltage
Device temperature
Setpoint value
0 to 9999.9
0 to 9999.9
k
/ bold = default setting
Interface parameters for RS422/485 (see interface description)
Value / settings
9600
19200
38400
8-1-none
8-1-odd
8-1-even
8-2-none
0 to 1 to 255
Description
This setting specifies the standard signal that should be out-
put.
Output does not emit signal.
Output emits the "Value to be output" in the form of a current
signal.
Output emits the "Value to be output" in the form of a voltage
signal.
This setting involves the selection of the value that should be
output at the analog output.
Example:
The load voltage can vary between 0 and 380 V depending on
the device type.
As the signal range is set per default to 0 to 9999.9, the end
value must be adjusted to 380.0 to make use of the full signal
range.
Note:
2
Load voltage
= load voltage squared
2
Load current
= load current squared
Lower limit for the "Value to be output"
Upper limit for the "Value to be output"
Description
Data bits-stop bits-parity check
According to Modbus specification, the address 0 is actually
not permitted. In the IPC 300 it is used to switch off the signal-
ing of a bus error.
Therefore if the power controller has an RS422/485 interface,
and this is not connected to an active bus, you can suppress
the "bus error" error message by changing the address to 0.
V1.00/EN/00741192/2021-03-30 [IPC 300]

Advertisement

Table of Contents
loading

This manual is also suitable for:

709051

Table of Contents