Electronic transformer, modbus interface description
Hide thumbs Also See for IPC 300:

Advertisement

Quick Links

JUMO IPC 300
Electronic transformer
Modbus interface description
70905100T92Z001K000
V1.00/EN/30048311/2023-02-25

Advertisement

Table of Contents
loading

Summary of Contents for JUMO IPC 300

  • Page 1 JUMO IPC 300 Electronic transformer Modbus interface description 70905100T92Z001K000 V1.00/EN/30048311/2023-02-25...
  • Page 3: Table Of Contents

    Contents Contents Introduction ..........5 Preface .
  • Page 4 Contents 5.2.3 Digital inputs/outputs............19 5.2.4 Controller .
  • Page 5: Introduction

    Introduction 1 Introduction Preface Read this operating manual before putting the device into operation. Keep the operating manual in a place that is accessible to all users at all times. Your comments are appreciated and may assist us in improving this operating manual. Warranty All necessary settings are described in this operating manual.
  • Page 6: Display Types

    1 Introduction Command sequence Config level -> Power controller -> Operating mode Small arrows between words are designed to make it easier to find parameters in the configuration level. DISPOSAL! At the end of its service life, the device and any batteries present do not belong in the trash! Please en- sure that they are disposed of properly and in an environmentally friendly manner.
  • Page 7: Connection Of The Interface

    1 Introduction Connection of the interface Terminating resistor of the RS422/485 serial interface To ensure problem-free operation of several devices in a line structure, their internal terminating resistors must be activated at the beginning and end. 1. Disconnect the device from the supply voltage 2.
  • Page 8: Configuration

    A set time of 0 ms means that the IPC 300 responds as quickly as possible. This setting should be de- ployed when using the RS422/485 interface.
  • Page 9: Protocol Description

    Device address The device address must lie in the range 1 to 255. Address 0 is reserved for broadcast messages, i.e., the instruction is executed by the IPC 300 but not answered. If an instruction with the device address 255 is received in the device, it will always be processed, even if a different device address has been configured.
  • Page 10: Chronological Sequence Of Communication

    Same duration as t1. Chronological sequence The master sends a data request for slave 1. After the last character is sent, all connected IPC 300 slaves wait for a time of t1. Then the instruction is evaluated. Slave 2 discards the instruction because the device address does not match. On the other hand, slave...
  • Page 11: Error Handling

    Minimum response time In the IPC 300, it is also possible to set a minimum response time of 0 to 500 ms in the configuration. The IPC 300 will not send back a response before this time elapses (measured since the last character was received), meaning the duration of t1 + t2 is extended accordingly.
  • Page 12: Detection Of Bus Errors

    2 Protocol description Error Error code for float values Measuring range underflow (Underrange) 0xFF800000 (Negative Infinity) Measuring range overflow (Overrange) 0x7F800000 (Positive Infinity) Other invalid value 0x7FC00000 (Not a Number) Detection of bus errors A bus error will be signaled if the device has an RS422/485 interface and a Modbus telegram is not re- ceived for at least 10 s.
  • Page 13: Functions

    Functions 3 Functions The following functions are available for the device: Function number Function Maximum number 0x03 or 0x04 Reading n words Max. 127 words (= 254 bytes) 0x06 Writing one word 1 word 0x10 Writing n words Max. 127 words (= 254 bytes) If the device receives an instruction with a different function number, it will respond with the Modbus error code 1 (ILLEGAL FUNCTION) in this case.
  • Page 14: Writing N Words

    3 Functions Example Write external inhibit input = 1 Modbus address = 0x00CD Instruction: D9F5 Response (same as instruction): D9F5 Writing n words This function is used to write n words starting at a specific address. Instruction Slave address Function Address Number of Number of Word values Checksum...
  • Page 15: Data Flow

    010302002D7859 4.1.2 Floating-point values In the case of Modbus float values, the IPC 300 operates with the IEEE-754 standard format (32 bits), the only difference being that byte 1 and 2 are interchanged with byte 3 and 4. SEEEEEE EMMMMMMM...
  • Page 16 4 Data flow...
  • Page 17: Address Tables

    (11 bytes) Software version 0x0006 text (13 bytes) VdN number 0x000D word (16 bits) Internal software version 0x000E text (9 bytes) Device name ("IPC 300") 0x0013 text (20 bytes) Fabrication number 0x001D text (9 bytes) Inspection ID 0x0023 word (16 bits) Reserve...
  • Page 18: Input And Output Variables

    5 Address tables Address Access Data type Signal designation 0x0098 R, W word (16 bits) Switch-off of display lighting (in min) 0x0099 R, W float Load voltage limit value (in V) 0x009B R, W float Current limit value (in A) 0x009D R, W float...
  • Page 19: Digital Inputs/Outputs

    5 Address tables 5.2.3 Digital inputs/outputs Address Access Data type Signal designation 0x00C9 bool Digital input 1 0x00CA bool Digital input 2 0x00CB bool Inhibit input 0x00CC bool Inhibit peak current 0x00CD R, W bool External inhibit input 0x00CE R, W bool External digital input 1 0x00CF...
  • Page 20 5 Address tables Address Access Data type Signal designation Bit1 Max. alarm Bit2 Load error Bit3 Load failure virtual current sensor 1 Bit4 Load failure external current sensor 2 Bit5 Load failure external current sensor 3 Bit6 Teach-In for load monitoring is missing Bit7 Fuse failure Bit8...
  • Page 21: Errors And Malfunctions

    5 Address tables Address Access Data type Signal designation Bit12 The voltage limitation is active Bit13 The current limiting is active Bit14 The power limitation is active Bit15 The resistance limitation is active 0x00F0 word (16 bits) Binary signal 2 Bit0 The voltage, current, power, or resistance limitation is active Bit1...
  • Page 22: Controlling The Analog Output

    5 Address tables Address Access Data type Signal designation 0x00F5 bool Wire break at external current sensor 1 0x00F6 bool Wire break at external current sensor 2 0x00F7 bool Wire break at external current sensor 3 0x00F8 bool Teach-In for load monitoring is missing 0x00F9 bool Fuse failure...
  • Page 23: Specification Of Values Via Interface

    Specification of values via interface 6 Specification of values via interface Setpoint specification If the setpoint value needs to be specified via the interface for a power controller, it must be configured accordingly. Using the keypad on the device or the setup program, navigate to: Configuration level >...
  • Page 24: External Inhibit Input And External Digital Input 1 And 2

    6 Specification of values via interface External inhibit input and external digital input 1 and 2 The external inhibit input (0x00CD) and the external digital inputs 1 (0x00CE) and 2 (0x00CF) can be written using the addresses 0x00CD-0x00CF. They can be used in exactly the same way as the hardware inhibit and digital inputs on the power con- troller, i.e., to block the power controller or for functions such as the keyboard lock or display switch-off.