2.3 Environmental influences
Incorrect use
Mounting site
Climatic
conditions
Power loss
IPC300 type
709051/X-XX-070... 400 V
709051/X-XX-100... 400 V
709051/X-XX-200... 400 V
V1.00/EN/00741192/2021-03-30 [IPC 300]
The device is not suitable for installation in potentially explosive areas.
The mounting site should be free from vibration, dust, and corrosive media.
In accordance with the conditions specified in VDE 0660-514, the device is
finger safe (IP20) and must be installed in a control cabinet.
- Relative humidity : 5 to 85 %, no condensation (3K3 according to EN
60721)
- Max. air inlet temperature 35 °C
- Ambient temperature range: 5 to 40 °C (3K3 according to EN 60721)
- Storage temperature range: -10 to 70 °C
Power loss occurs in the form of waste heat at the heat sink of the IPC 300, at
the mains filter, and choke, and has to be dissipated at the mounting site (e.g.
in the control cabinet) in accordance with the climatic conditions.
Voltage sup-
Maximum
ply
loss P
for
power
section
770 W
230 V
450 W
115 V
280 W
1100 W
230 V
115 V
1740 W
230 V
1400 W
115 V
power
Loss max.
640 W
400 W
960 W
2 Mounting
Power loss P
Loss
tion
of the applica-
21