Base Load; Ext. Current Sensor 2 And 3; Measurand - JUMO IPC 300 Operating Manual

Electronic transformer
Hide thumbs Also See for IPC 300:
Table of Contents

Advertisement

5 Configuration

Base load

0 to U
of the load voltage,
0 to I
of the max. load cur-
rent
0 to P
of the power
k
5.1.5

Ext. current sensor 2 and 3

Measurand

54
Note:
Nom
The base load setting depends on the subordinate control loop:
- For voltage: 0 to 100 % of the max. load voltage (e.g. 0 V)
- For current:
Nom
- For power:
Example:
Nom
/ bold = default setting
This setting configures which measurand is to be recorded.
Value / settings
Description
None
Switched off
Error current
By connecting an error current sensor, which outputs a standard
signal of 0 to 20 mA, for example, the system can be monitored
as regards an error current limit value.
The following values must be entered:
- Sensor output signal:
- Sensor input measuring range:
- Limit value error current
When a limit value is exceeded, there is an error message.
v Chapter 6.8 "External current sensors"
Load current
By connecting a load current sensor, which outputs a standard
signal of 0 to 20 mA, for example, the system can be monitored
as regards a load current limit value.
v Chapter 6.8 "External current sensors"
Mains current
By connecting a mains current sensor, which outputs a standard
signal of 0 to 20 mA, for example, the system can be monitored
as regards a mains current limit value.
v Chapter 6.8 "External current sensors"
k
/ bold = default setting
0 to 100 % of the max. load current (e.g. 0 A)
0 to 100 % of the power (e.g. 0 W)
P
Maximum
Output level: 3680 W
Base load: 680 W
0 mA
0 to 20 mA, 4 to 20 mA, customer-specific
0 to 500 mA, customer-specific
V1.00/EN/00741192/2021-03-30 [IPC 300]
3000W
0...20mA
Base load
Control signal