6.8.3 Mains current

V1.00/EN/00741192/2021-03-30 [IPC 300]
The mains current sensor serves to monitor the mains current and is placed in
the supply line upstream of the EMI filter. A passive current sensor with gal-
vanic isolation must be used.
h Install and connect current sensor in the voltage supply line
h Select measurand (mains current)
h Config.level
r
Ext.current sensors
mains current
h Select sensor output signal
h Config.level
r
Ext.current sensors
Outp.Signal e.g. 0 to 20 mA
h Config.level
r
Ext.current sensors
put.Measuring range e.g. 0 to 100 A
The current range 0 to 100 A is thereby assigned to the signal 0 to 20 mA.
Monitoring itself is performed via the limit value monitoring function, where the
mains current parameter can be found and has to be set. You can configure
the min., max., and hysteresis values here.
v Chapter 5.1.6 "Monitoring"