8 Error messages and alarms
Error message
IGBT short circuit
Pre-alarm
High temperature
Limitation
high temperature
Mains voltage
too low
Wire break
Current input
Wire break
Voltage input
Bus error
SiC voltage reserve
used up
Inhibit
(inhibit input)
Peak current too
high -> Inhibit
Inhibit
(external input)
80
Cause
IGBT defective
Note:
Monitoring only works when the load resis-
tance is so low that
controller nominal current (max. load cur-
rent) is flowing.
Device temperature is higher than 100 °C
(Excess temperature)
Device temperature is higher than 105 °C.
Device is too hot, output level is reduced!
(Limited power due to excess temperature)
DC intermediate circuit voltage is not with-
in specified tolerance range
v Chapter 10.1 "Voltage supply, load
current"
Input current too small for the set measur-
ing range.
Input voltage too small for the set measur-
ing range.
No connection to Modbus master or Mod-
bus master is inactive.
This message appears when the
power required by the setpoint specifica-
tion can no longer be reached with the load
present.
The firing pulse inhibit has been triggered
via a PLC level.
No power from the power controller.
The current monitoring module has sig-
naled an excessive peak current. To pre-
vent destruction of the device, a firing
pulse inhibit is briefly triggered.
The firing pulse inhibit has been triggered
via an interface.
Remedy
The device must be returned to JUMO
for repair.
- Return the device
2% of the power
- Ensure adequate ventilation or
- Reduce load current
- Use power controller with high-
- Check configured nominal volt-
v Chapter 5.1.2 "Power controller"
- Check wiring for wire breaks and
- Check upstream devices (con-
- Check wiring for wire breaks and
- Check upstream devices (con-
- Check wiring and master device
Note: This error message can be sup-
pressed by setting the device address
to "0".
- Replace SiC heating element
v Chapter 5.1.6 "Monitoring"
- Change control direction config-
v Chapter 5.1.7 "Binary inputs"
- Check wiring of the load circuit.
- If the error message is shown
v Interface manual "Ext. inhibit"
V1.00/EN/00741192/2021-03-30 [IPC 300]
provide for additional cooling
er maximum load current
age
reverse polarity.
trollers)
reverse polarity.
trollers)
(PLC).
uration
permanently, please contact the
JUMO Service team!