Setpoint Value Configuration; Monitoring - JUMO IPC 300 Operating Manual

Electronic transformer
Hide thumbs Also See for IPC 300:
Table of Contents

Advertisement

4 Operation

4.2.3 Setpoint value configuration

Value range
000.00
0 to U
of the load voltage
(U
the power section
-20 V)
Current load volt-
0 to P
age
of the power
(
P
0 to I
of the max. load current
0 to 100 %
of the output level
k

4.2.4 Monitoring

Current measured value
Current measured value
46
Max.
= voltage supply to
Max.
Max.
U
×
)
=
I
Max.
Max.
Nom.
Nom.
/ bold = default setting
The value to be monitored can be adjusted.
v Chapter 5.1.5 "Ext. current sensor 2 and 3"
The load voltage was used in this example.
Value range Description
0 to 9999.9
Absolute minimum limit values for load voltage, load current, pow-
er in W and kW, load resistance, DC intermediate circuit voltage, or
device temperature can be monitored.
v Chapter 5.1.5 "Ext. current sensor 2 and 3"
Example:
If the voltage falls below 20 V, an alarm is issued.
0 to 9999.9
Absolute max. limit values for load voltage, load current, power in
W and kW, load resistance, DC intermediate circuit voltage, or de-
vice temperature can be monitored.
v Chapter 5.1.5 "Ext. current sensor 2 and 3"
Example:
If the voltage exceeds 100 V, an alarm is issued.
Description
If "Value, adjustable" is configured as the error value, this
value is used in the event of a malfunction as the setpoint
value at the set analog input.
Note:
The base load setting depends on the subordinate control
loop:
- For voltage: 0 to 100 %
- For current:
0 to 100 % I
- For power:
0 to 100 % P
- None:
0 to 100 % of output level (e.g. 0 %)
Example:
P
Maximum
Output level: 3680 W
Base load: 680 W
0 mA
V1.00/EN/00741192/2021-03-30 [IPC 300]
U
(e.g. 0 V)
Max.
(e.g. 0 A)
Nom.
(e.g. 0 W)
Max.
3000W
0...20mA
Base load
Control signal
20 mA