Dangerous volt-
age
The electrical connection must only be carried out by qualified personnel! Dan-
gerous voltages will cause an electric shock in the event of contact with live
parts!
h Disconnect the system from the mains voltage on all poles.
All screw terminals supplied ex works must be inserted and screwed tight
during operation!
3.1 Screw connections in the power section
Tools
3.1.1 Type 709051/X-XX-070... or 709051/X-XX-100...
Terminal
C to N(V)
FB ground terminal
(Functional bonding)
V1.00/EN/00741192/2021-03-30 [IPC 300]
- Screwdriver
- Hex wrench size 5 mm
Version
Hex socket screws
wrench size 5 mm
Cable with ferrule
Hexagon nut
wrench size 13 mm
3 Electrical connection
Conductor
cross
section
2
10 to 50 mm
Cable lug with
hole: 8.4 mm
Maximum
tightening
torque
6 to 8 Nm
9 Nm