Controlling The Analog Output - JUMO IPC 300 Operating Manual

Electronic transformer, modbus interface description
Hide thumbs Also See for IPC 300:
Table of Contents

Advertisement

5 Address tables
Address
0x00F5
0x00F6
0x00F7
0x00F8
0x00F9
0x00FA
0x00FB
0x00FC
0x00FD
0x00FE
0x00FF
0x0000
0x0101
0x0102
0x0103
0x0104
0x0105
0x0106
0x0107
0x0108
0x0109
0x010A
0x010B
0x010C
0x010D
0x010E
0x010F
0x0110
5.2.8

Controlling the analog output

Address
0x0111
0x0113
0x0115
22
Access
Data type
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
R
bool
Access Data type Signal designation
R
float
Reserve
R, W
float
Value of analog output when controlled via interface (in %)
R
bool
Reserve
Signal designation
Wire break at external current sensor 1
Wire break at external current sensor 2
Wire break at external current sensor 3
Teach-In for load monitoring is missing
Fuse failure
IGBT break
IGBT short-circuit
Limited power due to excess temperature
Pre-alarm due to excess temperature
Mains voltage too low
Wire break at current input
Wire break at voltage input
Bus error
Reserve
Energy meter configuration is incorrect
SiC voltage reserve exhausted
Inhibit via inhibit input
Inhibit via peak current
Inhibit via external input
Inhibit via U
– detection 1
CE sat
Inhibit via U
– detection 2
CE sat
Error current too large
Failure of fan 1
Failure of fan 2
Invalid configuration
Defect in external current sensor 2
Defect in external current sensor 3
Configuration error in external current sensor (2 and/or 3)