Binary Signal For Collective Fault - JUMO IPC 300 Operating Manual

Electronic transformer
Hide thumbs Also See for IPC 300:
Table of Contents

Advertisement

8.1 Binary signal for collective fault

V1.00/EN/00741192/2021-03-30 [IPC 300]
This signal is used for controlling the digital output and LED K1, and can also
be read out via the interfaces of the power controller.
You can use the setup program to configure which events (alarm and error
messages) are to be grouped together as a binary signal for the collective
fault.
All fault messages are OR-linked and output as a binary signal for a collective
fault on the relay output or optocoupler.
In addition, LED K1 lights up yellow.
This alarm can switch a relay at the digital output.
v Chapter 5.1.8 "Binary output"
8 Error messages and alarms
83