SPC Series Solar Pump Inverter
Function
code
Lag frequency
P15.22
P15.23
Name
synchronously.
needs to be greater than P15.19 so that
the system can report the underload
alarm when the underload run time is
reached and then reset can be performed
when the time (P15.21–P15.19) elapsed.
If the value of P15.21 is the same as that
of P15.19, auto reset is performed at the
same time as the underload alarm is
reported.
0.00–200.00Hz
P15.22
used to determine the underload run
condition. Currents are compared only
threshold
when the absolute value of target
frequency minus ramp frequency is
continuously less than or equal to this
parameter.
0.0–3600.0s
Time setting on weak-light delay.
When the output frequency is less than
or equal to the PI output frequency lower
limit and the delay counting is started,
which reaches the weak-light delay time,
the system reports the weak-light alarm
(A-LS)
Weak-light
non-continuous
delay
counter is automatically cleared.
Note: When the bus voltage is lower than
the undervoltage point or the PV voltage
is lower than 70V, the system directly
reports the weak-light alarm without any
delay.
When P15.32=0, in weak-light condition,
the system automatically switch to the
power-frequency input mode.
Description
Generally,
is the lag frequency threshold,
and
then
sleeps.
situation,
-44-
Function parameter list
Default Modify
the
value
0.30Hz
In
the
the
delay
100.0s