INVT SPC Series Operation Manual page 55

Solar pump inverter
Table of Contents

Advertisement

SPC Series Solar Pump Inverter
Fault code
UV
OL1
OL2
SPO
OH2
EF
CE
Fault type
Bus undervoltage
fault
Motor overload
Inverter overload
Phase loss on
output side
Inverter module
overheat
External fault
RS485
communication
fault
Possible cause
The voltage of the
grid is too low.
The overvoltage stall
protection is not
enabled.
The grid voltage is
too low.
The motor rated
current is set
incorrectly.
The motor stall
occurs or the load
transient is too large.
The ACC is too fast.
The rotating motor is
reset.
The grid voltage is
too low.
The load is too
heavy.
The motor power is
too small.
Phase loss output
occurs to U, V, W (or
the three phases of
the load are seriously
asymmetrical).
Air duct jam or fan
damage occurs.
Ambient temperature
is too high.
The time of overload
running is too long.
SI external faulty
input terminal action.
The baud rate setting
is incorrect.
A fault occurs to the
-51-
Fault diagnosis and solution
Solution
Check the grid input
power supply.
Check the setting of
related function codes.
Check the grid voltage.
Reset the motor rated
current.
Check the load and
adjust the torque boost
quantity.
Increase the ACC time.
Avoid the restarting
after stop.
Check the grid voltage.
Select an inverter with
larger power.
Select a proper motor.
Check the output
wiring.
Check the motor and
cables.
Dredge the vent duct or
replace the fan.
Lower the ambient
temperature.
Check external device
input.
Set a proper baud rate.
Check the
communication