SPC Series Solar Pump Inverter
Function
code
P00.01
Max. output
P00.03
Upper limit of
P00.04
Name
torque accuracy, without the need to
install pulse encoders.
2: Space voltage vector control mode
Applicable to scenarios without
demanding requirements on control
accuracy, such as fan and pump. One
inverter can drive multiple motors.
Used to select the channel of running
inverter control commands.
The inverter control commands include
the start, stop, forward run, reverse run,
and fault reset commands.
0: Keypad (LOCAL/REMOT off)
The commands are controlled through
keypad keys, such as the RUN and
Channel of
STOP/RST keys. In running state, you
running
can press both RUN and STOP/RST to
commands
enable the inverter to coast to stop.
1: Terminal (LOCAL/REMOT blinking)
The running commands are controlled
through multifunction input terminals.
2: Communication (LOCAL/REMOT on)
The running commands are controlled by
the upper computer in communication
mode.
Used to set the max. output frequency of
the inverter. Pay attention to the function
code because it is the foundation of the
frequency setting and the speed of
frequency
acceleration (ACC) and deceleration
(DEC).
Setting range: P00.04–400.00Hz
The upper limit of the running frequency
is the upper limit of the output frequency
running
of the inverter, which is lower than or
frequency
equal to the max. output frequency.
When the set frequency is higher than
Description
-20-
Function parameter list
Default Modify
○
1
◎
110.00Hz
◎
110.00Hz