SPC Series Solar Pump Inverter
Function
code
Lower limit of
P00.05
Setting channel
P00.06
of A frequency
Frequency set
P00.10
through keypad
P00.11
ACC time 1
P00.12
DEC time 1
P00.13
Name
the upper limit of the running frequency,
the upper limit of the running frequency is
used for running.
Setting range:
output frequency)
The lower limit of the running frequency
is the lower limit of the output frequency
of the inverter,
When the set frequency is lower than the
lower limit of the running frequency, the
lower limit of the running frequency is
running
used for running.
frequency
Note: Max. output frequency ≥ Upper
limit of frequency ≥ Lower limit of
frequency
Setting range:
limit of running frequency)
0: Keypad
1–7: Reserved
8: Modbus communication
command
Setting range: 0–8
0.00
ACC time means the time needed if the
inverter speeds up from 0Hz to the max.
output frequency (P00.03).
DEC time means the time needed if the
inverter speeds down from the max.
output frequency (P00.03) to 0Hz.
Setting range of
3600.0s
0: Run at the default direction. The
inverter
Running
direction.(FWD/REV off)
direction
1: Run at the opposite direction. The
inverter
(FWD/REV on)
Description
P00.05–P00.03
0.00Hz–P00.04
Hz–P00.03
(Max. output frequency) 110.00Hz
P00.11
runs
runs
in
reverse
-21-
Function parameter list
(Max.
(Upper
and P00.12: 0.0–
in
forward
direction.
Default Modify
◎
0.00Hz
○
0
○
Model
○
depended
Model
○
depended
○
0